Vector SIMOVERT MASTERDRIVES 6SE70 VC Provozní pokyny Strana 42

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 162
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 41
Installation in Conformance with EMC Regulations Vector Control Chassis Type Frequency Converter
476 869 4070 76 J AB-74 Siemens AG
6-2 Operating Instructions SIMOVERT MASTERDRIVES
Use a noise suppression filter in the incoming powerline.
Connect the noise suppression filter to ground and to the converter
through a large surface area.
It is best to directly mount the noise suppression filter on the same
good conductive mounting surface as the converter or inverter.
You must insert a line reactor between the noise suppression filter
and the unit.
Contactor operating coils that are connected to the same supply
network as the rectifier unit or that are located in the close proximity
of the rectifier unit must be connected to overvoltage limiters (e.g.
RC circuits, varistors).
You will find further information in the brochure "Installation Instructions
for EMC-correct Installation of Drives" (Order No.: 6SE7087-6CX87-
8CE0).
Zobrazit stránku 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 ... 161 162

Komentáře k této Příručce

Žádné komentáře