Maintenance Vector Control Chassis Type Frequency Converter
476 869 4070 76 J AB-74 Siemens AG
12-4 Operating Instructions SIMOVERT MASTERDRIVES
12.3 Replacing the fan transformer fuse -F3, -F4 (type K)
Construction type K: Fuses -F3, -F4
The fuses are in a fuse holder which is arranged below the fan in front
of the air baffle plate. To replace the fuses, the fuse holder has to be
opened.
Fig. 12-3 Fan transformer (-T10), fan transformer fuses (-F3, -F4)
12.4 Replacing the fan transformer
The fan transformer is screwed on behind the motor connection.
Mark the connecting cables on the transformer and disconnect
them.
Undo the screw connections at the bottom on the transformer plate
and remove the transformer.
Type K: Secure the transformer against falling down!
Install the new transformer in the reverse sequence.
Construction types
E - G
Construction type K